Overheating datacenter stopped 2.5 million bank transactions
- Reference: 1699360090
- News link: https://www.theregister.co.uk/2023/11/07/overheating_datacenter_singapore/
- Source link:
DBS and Citibank, the banks involved, experienced outages in the mid-afternoon of October 14, 2023 that resulted in full or partial unavailability of online banking apps for around two days – leaving customers and vendors without a way to make payments in a city-state that is increasingly reliant on digital financial systems.
In fact, according to minister Alvin Tan in a [1]parliamentary reply , the outages led to 810,000 failed attempts to access the two platforms while 2.5 million payment and ATM transactions could not be completed.
[2]
The root cause of the outages was issues in the cooling system that caused the temperature to rise above optimal operating range at the Equinix datacenter used by both institutions.
[3]
[4]
Equinix has [5]reportedly blamed a contractor, alleging that person "incorrectly sent a signal to close the valves from the chilled water buffer tanks" during a planned system upgrade.
Upon the outage, both banks immediately activated IT disaster recovery and business continuity plans.
[6]
"However," according to Tan, "both banks encountered technical issues which prevented them from fully recovering their affected systems at their respective backup datacenters – DBS due to a network misconfiguration and Citibank due to connectivity issues."
Tan concluded that the two banks had "fallen short" of MAS requirements to ensure critical IT systems are resilient. The authority requires that unscheduled downtime for critical systems affecting bank operations should not exceed four hours within any 12 month period – a limit easily exceeded in this case.
As a result, the MAS has slapped DBS with some hefty [7]punishments – including barring it over the next six months from reducing the size of its branch and ATM network, making any non-essential IT changes, or acquiring new business ventures.
[8]
DBS is also required to apply a multiplier of 1.8 times to its risk-weighted assets for operational risk.
[9]Singapore's government writes a standard for datacenter ops in the tropics
[10]Facebook and Singapore teams looking for ways to get data centres relaxing in moist tropical climes
[11]Alibaba takes more of Salesforce behind the great firewall
[12]Singapore gives banks two-week deadline to fix SMS security
Singapore-based Acronis CISO Kevin Reed told The Register it was surprising the cooling system was not redundant, as were the banks failed backup plans.
"As is often the case, an incident is not a single failure, but a chain of interconnected events. Usually, a properly implemented failover takes seconds or minutes," he lamented to The Reg on Tuesday.
In a [13]LinkedIn post , Reed called it "odd" that such a core system like the handling of authentication for an online bank would be managed by a third-party provider.
MAS does not oversee external providers to banks, such as Equinix.
Overheating of a datacenter is an unfortunate event in a country that literally [14]wrote the standard for datacenter operations in the tropics.
Such standards – as well as successful implementation of them – will only become more important as extreme weather takes hold globally.
In addition to the need to keep datacenters cool and backup systems resilient, it's vital to recognize the challenges inherent in full reliance on digital systems, according to Tan.
"While we want to be digital first (in) our approach to digitalization, we cannot be digital only," he declared in parliament on Monday.
He advocated for consumers and businesses to be aware that sometimes these systems do not operate smoothly, and to provide other forms of payment for the continuity of economic participation. ®
Get our [15]Tech Resources
[1] https://www.mas.gov.sg/news/parliamentary-replies/2023/oral-reply-to-parliamentary-question-onbanking-services-disruption-of-dbs-and-citibank
[2] https://pubads.g.doubleclick.net/gampad/jump?co=1&iu=/6978/reg_onprem/front&sz=300x50%7C300x100%7C300x250%7C300x251%7C300x252%7C300x600%7C300x601&tile=2&c=2ZUptMnT0kzuSlmo4cyDlUQAAANM&t=ct%3Dns%26unitnum%3D2%26raptor%3Dcondor%26pos%3Dtop%26test%3D0
[3] https://pubads.g.doubleclick.net/gampad/jump?co=1&iu=/6978/reg_onprem/front&sz=300x50%7C300x100%7C300x250%7C300x251%7C300x252%7C300x600%7C300x601&tile=4&c=44ZUptMnT0kzuSlmo4cyDlUQAAANM&t=ct%3Dns%26unitnum%3D4%26raptor%3Dfalcon%26pos%3Dmid%26test%3D0
[4] https://pubads.g.doubleclick.net/gampad/jump?co=1&iu=/6978/reg_onprem/front&sz=300x50%7C300x100%7C300x250%7C300x251%7C300x252%7C300x600%7C300x601&tile=3&c=33ZUptMnT0kzuSlmo4cyDlUQAAANM&t=ct%3Dns%26unitnum%3D3%26raptor%3Deagle%26pos%3Dmid%26test%3D0
[5] https://www.businesstimes.com.sg/companies-markets/telcos-media-tech/contractor-error-caused-server-outage-behind-dbs-citi-banking
[6] https://pubads.g.doubleclick.net/gampad/jump?co=1&iu=/6978/reg_onprem/front&sz=300x50%7C300x100%7C300x250%7C300x251%7C300x252%7C300x600%7C300x601&tile=4&c=44ZUptMnT0kzuSlmo4cyDlUQAAANM&t=ct%3Dns%26unitnum%3D4%26raptor%3Dfalcon%26pos%3Dmid%26test%3D0
[7] https://www.theregister.com/2023/11/06/asia_in_brief/
[8] https://pubads.g.doubleclick.net/gampad/jump?co=1&iu=/6978/reg_onprem/front&sz=300x50%7C300x100%7C300x250%7C300x251%7C300x252%7C300x600%7C300x601&tile=3&c=33ZUptMnT0kzuSlmo4cyDlUQAAANM&t=ct%3Dns%26unitnum%3D3%26raptor%3Deagle%26pos%3Dmid%26test%3D0
[9] https://www.theregister.com/2023/06/12/singapore_tropical_datacenter_standard/
[10] https://www.theregister.com/2021/06/18/facebook_singapore_data_centre/
[11] https://www.theregister.com/2023/11/06/asia_in_brief/
[12] https://www.theregister.com/2022/01/20/singapores_monetary_authority_requires_banks/
[13] https://www.linkedin.com/pulse/thoughts-dbs-availability-incident-kevin-reed/
[14] https://www.theregister.com/2023/06/12/singapore_tropical_datacenter_standard/
[15] https://whitepapers.theregister.com/
Shouldn't that be Sangapore or maybe even Sungapore?
cheek, you let my tongue escape!
Reed called it "odd" that such a core system like the handling of authentication for an online bank would be managed by a third-party provider.
If it can be outsourced it will be outsourced. Nothing odd about that these days.
Backup?
If your backup datacentre doesn't function properly, it's not a backup at all, it's nothing more than a waste of money.
Maybe test these things once in a while?
This is what happens when you have unmanned DataCenters
Been to many "unmanned Datacenters", when i say unmanned you just deal with a security guard who's job is just that, nothing more, that's the only monitoring that is going on. Servers could be cooking for all they know or crashing. I have walked past racks that have been bleeping for weeks or red fault lights blinking away till the led gives up.
Re: This is what happens when you have unmanned DataCenters
I get your point but the DCs should have correct monitoring for those possibilities. Also inert gas fire suppression isn't compatible with meatsacks.
I once got a bollocking for being in the DC of a catalogue based high street retailer. They didn't know we were working in there. They also didnt think to question how their security had let us in tho.
Re: This is what happens when you have unmanned DataCenters
You don't need inert gas suppression to completely reduce oxygen levels to lethality. Very little burns at 16% oxygen levels and some DCs run 17% by default (yes, you DO feel it and it affects mental processes)
Global warming???
I visited regularly, lived and worked in Singapore since 1979. Its hotter in the city because of all the concreteand heat from the traffic. But it's no warmer anywhere else. And it's on the equator FFS. Is that the best you can do?
...the valves...
There's your problem.
Oh, maybe I will admit to taking this out of context :)
> Running infrastructure in the tropics has its challenges – but so do failed disaster recovery plans
So the plans were Singapore then...